从STERIS资料归纳空间VHP去污染设备选型与URS要点
选择适合的空间VHP去污染设备
一篇微信公众号文章归纳STERIS Life Sciences关于设施生物去污染VHP系统实施的资料,比较集成式与便携式VHP发生器的适用条件。文章按使用频次区分集成式与便携式、管道式与无管道式发生器,并说明VHP的一次分配由发生器完成,二次分配可借助房间内布置的喷嘴或空调系统。
当考虑将VHP(Vaporized Hydrogen Peroxide,汽化过氧化氢
)去污染的方式用于洁净区房间的消毒时,如何基于车间产线布局、HVAC系统布局,以及产线生产工艺流,选择、设计适合的VHP系统?
本文从STERIS Life Sciences的一份资料中,总结一些内容供思考。
VHP equipment is generally divided into two different categories; integrated and portable units. They vary in how VHP is injected, contained, evenly distributed and purged from an enclosure. For example, if the process demands frequent biodecontamination, an integrated VHP system would be the best choice. Integrated systems minimise set-up time and effort, and offer the fastest cycle times. They also provide a single pass source of VHP to decontaminate one or multiple zones automatically without the use of manually placed fans.如果VHP频繁使用,则通常安装集成式的,不涉及太多的人员操作。
Non-piped portable VHP generators require no permanent installation and are always deployed inside a room or suite, alone or networked with others. If the rooms have a complex layout or are filled with equipment, fans may need to be positioned to enhance the distribution. 如果房间内有生产设备,则可能需要借助风扇加强VHP的分布。Non-piped VHP generators typically have longer redeployment times, as they remain in a room during the aeration phase of the biodecontamination cycle. Thus, they are often best suited for less frequent use.无管道便携式VHP发生器的使用效率低,因为只能等通风程序结束后才可以进入房间取出设备。Piped VHP portable generators are typically placed outside the room and VHP is piped in through a port. The lower airflow of a piped generator increases the need for well-placed fans. However, unlike the non-piped VHP generator, it can be redeployed to decontaminate another enclosure as the first one aerates.带有管道的便携式发生器就不存在上述所说的缺点,它可以在一个区域进入通风阶段时,通过切换管路就可以进行下一个区域的VHP。
Air is the medium which transports VHP from the generator to all surfaces within the target enclosure. Its temperature, volume and humidity determine VHP concentration, distribution and physical state. Condensation along this pathway should be avoided. Hydrogen peroxide remains as a vapour with proper temperature and relative humidity control and flows with the air streams designed into the application.空气是递送汽化过氧化氢的媒介,空气的温度、湿度、量是决定汽化过氧化氢浓度、分布、物理状态的关键因素,确保使得汽化过氧化氢在传输阶段不会产生冷凝现象。
This distribution process can be broken down into two categories:
Primary distribution: The point where liquid peroxide is vaporised and moved at a high concentration, typically through an insulated(隔热的) polymer pipe.
For a portable non-piped generator the primary distribution is in the generator itself. An internal blower will disperse the VHP in the surrounding environment.对于无管路的便携式发生器,汽化过氧化氢的一次分配依靠的是设备自身配置的鼓风机。
Piped generators can be designed to deliver VHP into and adjacent room or enclosure or one that is hundreds of feet away. Larger applications use manifolds and an array of insulated polymer pipes to deliver the highly concentrated VHP to the target enclosure.
Secondary distribution: The point when highly concentrated VHP is diluted into the cooler air inside the enclosure and dispersed to decontaminate all exposed surfaces. Secondary distribution can be achieved with the use of well-positioned injection ports in a room or use the target area HVAC system. Manually placed fans are a less desirable, although a viable option.汽化过氧化氢的二次分配依靠的是房间内布置的喷嘴或空调系统,不推荐使用移动的风扇。It is useful if the footprint of the HVAC system matches that of the VHP target zone. VHP处理的区域如果是独立的空调系统,则比较方便通过空调系统进行二次分配。Both single pass and recirculating HVAC systems can be used as a means of secondary distribution and aeration.
A process-oriented URS focuses on production or process success factors such as turnover time, process efficacy, consistency, cost, safety etc. A proactive process may contain many items to consider:
- Zones and frequency
- List the facility's individual "target" zones, their volume, the expected frequency of VHP biodecontamination and the acceptable cycle time that will support planned operations. 搞清楚进行VHP处理区域的空间体积、频次、可接受的单次处理时间。Additional requirements here might include treating different rooms/zones in close sequence, or in groups. 如果洁净区布置多条产线,且有公用区域(如多条灌装线共用配液线),还要结合工艺流程、排产计划等,综合考虑区域VHP处理的顺序,以及某个区域单独处理还是合并处理的设计问题。
- Floor plan
- Include a floor plan that identifies the perimeters of the target rooms. Indicate if groups of rooms should be treated at once and provide the room classification. Mark acceptable locations where VHP equipment can be deployed. Note that only portable, non-piped units are positioned inside the target area. If the groups of rooms are not adjacent to one another show a plan view indicating their proximity. It is best to control airflow where the footprint of the HVAC and the target zone align. If only the floor area is shown, add ceiling height or room volume. Then identify any specific enclosures within the space that may need individual biodecontamination such as the incubators.预先弄清楚洁净区级别设定、区域面积高度、必须放置便携式发生器的位置。最好对齐空调系统和VHP灭菌二者的区域。还要考虑某些功能间的特殊性,可能需要单独设计VHP。
- HVAC
- The HVAC system always plays a critical role in the secondary distribution of VHP and/or aeration. Provide a description of the HVAC system including air exchanges/hour, airflow rates, maximum per cent make up air and perhaps most importantly the coverage or footprint as it relates to the target zone. Include an HVAC schematic/P&ID and identify if it is single pass or recirculating, any drying systems, noise reducers or other components in line with the system. Provide materials of construction for the HVAC system, ducting and the verify its alignment with the VHP target zone.预先弄清楚空调系统的性能设计,区域布置,材质是否都耐受过氧化氢。
- Sequencing and redundancy
- Consider the utilisation of the VHP equipment. For example, a generator can be used to decontaminate a material airlock or pass through during working hours and a cleanroom suite overnight. Determine if it makes sense to include redundancy in the system. For example, a backup VHP generator can be attached to a common manifold to serve multiple rooms or provide the flexibility to decontaminate multiple spaces at the same time.结合车间生产的工作流,考虑VHP设备的使用顺序,既考虑设备间的互相备份,也不过多配置。
- Safety requirements
- Safety considerations should be clearly outlined in a URS. This may include hydrogen peroxide concentration sensors within the target area and monitors in adjacent spaces. Also consider other safety mechanisms, such as automatic door locks, warning lights, E-Stops, alarms for differential pressure monitoring, and limit switches to verify valve positions on a distribution manifold. 应考虑安全问题,在VHP处理区域和临近区域都应监测浓度,同时应设计紧急情况下的自动处理机制(自动锁门、报警提示等)。
- Regulatory Requirements
- CFR 21-Part 11 compliance, including user administration, audit trail, print, alarm and trend logs.考虑VHP设备数据完整性的合规问题。
- Consumables
- Is the consumable registered with the EPA or the EU BPR? Do lot numbers and expiration dates need to be automatically transferred into an internal data management system? What is the anticipated consumable consumption? What storage provisions need to be made? 需要考虑VHP设备所搭配使用的物料的法规符合性。
当自己不够专业时,就更需要一个专业的伙伴。当寻找VHP设备/设施的供应商时,看看他们所提供的问卷内容,就可以基本知道他们的专业水平了。
Quote from "Guide to implementing a VHP system for facility biodecontamination", by STERILE Life Sciences